Series 100-180kVA trium input tres output plene digitalis imperium online duplex conversio tres input tres output UPS lineamenta alta altiore efficientia, princeps potentiae input factor, humilis input vena harmonica, et qualitas output optima. Potestas varias difficultates emissionis tollere ac clientes stabili ac certa potentia praesidii praebere.
Producti nostri amplis applicationibus habent, ut tuta, stabilis, certa, et amicabilis potentia copia subsidiorum criticorum onerum in variis industriis praebeat, sicut telecommunicationum, oeconomicorum, educationis, translationis, emissionis, sanitatis, et fabricationis.
Potentia dolor: 100-180KVA
Modus operating: Tres initus, tres outputs
• Ultra-wide input range voltage, apta ad duram potentiam eget ferendum
• Wide input frequency range, compatitur cibus generantibus
• Super efficientiam ≥ 95.5%
• Input potentia factor usque ad 0.99, input current harmonica <3%
• Fortis onus facultatem, condiciones oneris aptissimas, compatible cum generante operatione
• sustinet non-canus probatio onus
• subsidia parallela nexus 4 unitates communicantes altilium pack
• generantibus subsidia
• 4.3-inch color touchscreen, facile ad operandum
• administratio intelligentis functiones, subsidia RS485, SNMP, kilonode et CAN interfaces
| Categoria | Parameter | YT-UT 33100 | 33120 | 33160 | 33180 |
|---|---|---|---|---|---|
| capacitas | Rated Capacity (kVA) | 100 | 120 | 160 | 180 |
| Input | Wiring System | 3-Phase 5-Wire | |||
| Rated Input Voltage | 380/400/415Vac | ||||
| Input intentione dolor | 138~485Vac | ||||
| Input Frequency Range | 40Hz-70Hz | ||||
| Input Power Factor | ≥0.99 | ||||
| Input Current THDi | ≤3% (C% onere lineari) | ||||
| Bypass intentione dolor | 220Vac superior: 25% (+10%, +15%, +20% opt); 230Vac superior: 20% (+10%, +15% opt); 240Vac superior: 15% (+10% opt); Inferior: -45% (-10%,-20%,-30% opt) | ||||
| Generator Connection | Supported | ||||
| Output | Wiring System | 3-Phase 5-Wire | |||
| Rated Output intentione | 380/400/415Vac | ||||
| Output Power Factor | 0.9 | ||||
| Voltage Accuracy | ±1% | ||||
| Frequentia | Modus mains: ±1%/±2%/±4%/±5%/±10% commodabilis; Pugna modus: (50/60±0.1%)Hz | ||||
| Current Crest Ratio | 3:1 | ||||
| Output intentione THDv | ≤2% (100% onere lineari); ≤4% (C% non-linearibus onus) | ||||
| Altiore Efficens | 95.5% | ||||
| Overload Capacity | 110% onus: 60min → bypass; 125% onere: 10min → praeterire; 150% onus: 1min → bypass | ||||
| Pugna | Pugna intentione | ±180/192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30-50 cellulae ad libitum) | |||
| dato currente | Max 30A | ||||
| TRANSFERENDIS | Transfer Tempus | Mains to bypass: 0ms (track); Mains in altilium: 0ms | |||
| Environment | Operating Temperature | 0°C ~ 40°C | |||
| Repono Temperature | -25°C ~ 55°C | ||||
| Umor dolor | 0~ XCV% (non-condensatione) | ||||
| Altitude operating | <150m | ||||
| Vox (dB ad 1m) | <60 | ||||
| Munera | Terror functiones | ONERO, mains deprauatio, UPS culpa, altilium undervoltage, etc. | |||
| Praesidium functiones | Pugna undervoltage, output over/under intention, short circuit, overload, over temperies, fan culpa terror, impetus impetus | ||||
| Communication Interfaces | CAN, RS485, FE, LBS, card parallela, SNMP adaptor (opt), Nullam card (opt) | ||||
| Corporalis | Dimensiones (D×W×H mm) | 885×440×1200 | |||
| Net Pondus (kg) | 160 | 162 | 196 | 198 | |