+86 13012999975

The 100-180kVA series of three-input three-output fully digital control online double-conversion three-input three-output UPS features high overall efficiency, high input power factor, low input current harmonics, and excellent output quality. It can eliminate various power grid problems and provide customers with stable and reliable power protection.
Our products have a wide range of applications, providing safe, stable, reliable, and environmentally friendly power supply for critical loads in various industries such as telecommunications, finance, education, transportation, broadcasting, healthcare, and manufacturing.
Power Range: 100-180KVA
Operating Mode: Three inputs, three outputs
• Ultra-wide input voltage range, adaptable to harsh power grid environments
• Wide input frequency range, compatible with fuel generators
• Overall efficiency ≥ 95.5%
• Input power factor up to 0.99, input harmonic current < 3%
• Strong load capacity, highly adaptable to load conditions, compatible with generator operation
• Supports no-load aging testing
• Supports parallel connection of 4 units and sharing a battery pack
• Supports generators
• 4.3-inch color touchscreen, easy to operate
• Intelligent management functions, supports RS485, SNMP, kilonode, and CAN interfaces
| Category | Parameter | YT-UT 33100 | 33120 | 33160 | 33180 |
|---|---|---|---|---|---|
| Capacity | Rated Capacity (kVA) | 100 | 120 | 160 | 180 |
| Input | Wiring System | 3-Phase 5-Wire | |||
| Rated Input Voltage | 380/400/415Vac | ||||
| Input Voltage Range | 138~485Vac | ||||
| Input Frequency Range | 40Hz-70Hz | ||||
| Input Power Factor | ≥0.99 | ||||
| Input Current THDi | ≤3% (100% linear load) | ||||
| Bypass Voltage Range | 220Vac upper: 25% (+10%,+15%,+20% opt); 230Vac upper: 20% (+10%,+15% opt); 240Vac upper: 15% (+10% opt); Lower: -45% (-10%,-20%,-30% opt) | ||||
| Generator Connection | Supported | ||||
| Output | Wiring System | 3-Phase 5-Wire | |||
| Rated Output Voltage | 380/400/415Vac | ||||
| Output Power Factor | 0.9 | ||||
| Voltage Accuracy | ±1% | ||||
| Frequency | Mains mode: ±1%/±2%/±4%/±5%/±10% adjustable; Battery mode: (50/60±0.1%)Hz | ||||
| Current Crest Ratio | 3:1 | ||||
| Output Voltage THDv | ≤2% (100% linear load); ≤4% (100% non-linear load) | ||||
| Overall Efficiency | 95.5% | ||||
| Overload Capacity | 110% load: 60min → bypass; 125% load: 10min → bypass; 150% load: 1min → bypass | ||||
| Battery | Battery Voltage | ±180/192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30-50 cells optional) | |||
| Charging Current | Max 30A | ||||
| Transfer | Transfer Time | Mains to bypass: 0ms (tracking); Mains to battery: 0ms | |||
| Environment | Operating Temperature | 0°C ~ 40°C | |||
| Storage Temperature | -25°C ~ 55°C | ||||
| Humidity Range | 0~95% (non-condensing) | ||||
| Operating Altitude | <1500m | ||||
| Noise (dB at 1m) | <60 | ||||
| Functions | Alarm Functions | Overload, mains abnormality, UPS fault, battery undervoltage, etc. | |||
| Protection Functions | Battery undervoltage, output over/under voltage, short circuit, overload, over temperature, fan fault alarm, surge protection | ||||
| Communication Interfaces | CAN, RS485, FE, LBS, parallel card, SNMP adapter (opt), relay card (opt) | ||||
| Physical | Dimensions (D×W×H mm) | 885×440×1200 | |||
| Net Weight (kg) | 160 | 162 | 196 | 198 | |
| Standard | Applicable Standard | YD/T 1095-2018 |