+86 13012999975

Seri 100-180kVA saka telung-input telung-output kontrol digital kanthi online konversi dobel telung-input telung-output UPS nduweni efisiensi sakabèhé dhuwur, faktor daya input dhuwur, harmonik arus input sing sithik, lan kualitas output sing apik banget. Bisa ngilangi macem-macem masalah kothak daya lan nyedhiyakake proteksi daya sing stabil lan dipercaya.
Produk kita duwe macem-macem aplikasi, nyedhiyakake pasokan listrik sing aman, stabil, dipercaya, lan ramah lingkungan kanggo beban kritis ing macem-macem industri kayata telekomunikasi, keuangan, pendidikan, transportasi, penyiaran, perawatan kesehatan, lan manufaktur.
Range daya: 100-180KVA
Mode operasi: Telung input, telung output
• Range voltase input Ultra-sudhut, adaptasi kanggo lingkungan kothak daya atos
• Jangkoan frekuensi input Wide, kompatibel karo generator bahan bakar
• Efisiensi sakabèhé ≥ 95,5%
• Faktor daya input nganti 0,99, arus harmonik input < 3%
• Kapasitas beban sing kuat, bisa adaptasi banget kanggo kondisi mbukak, kompatibel karo operasi generator
• Ndhukung testing tuwa ora mbukak
• Ndhukung sambungan podo karo 4 Unit lan nuduhake Pack baterei
• Ndhukung generator
• 4.3-inch werna demek, gampang kanggo operate
• Fungsi manajemen cerdas, ndhukung antarmuka RS485, SNMP, kilonode, lan CAN
| kategori | Paramèter | YT-UT 33100 | 33120 | 33160 | 33180 |
|---|---|---|---|---|---|
| Kapasitas | Kapasitas Rated (kVA) | 100 | 120 | 160 | 180 |
| Input | Sistem Wiring | 3-Fase 5-Kawat | |||
| Dirating Tegangan Input | 380/400/415Vac | ||||
| Range Tegangan Input | 138~485Vac | ||||
| Rentang Frekuensi Input | 40Hz-70Hz | ||||
| Faktor Daya Input | ≥0.99 | ||||
| Input Saiki THDi | ≤3% (100% beban linier) | ||||
| Range Tegangan Bypass | 220Vac ndhuwur: 25% (+ 10% + 15% + 20% milih); 230Vac ndhuwur: 20% (+ 10% + 15% milih); 240Vac ndhuwur: 15% (+ 10% milih); Ngisor: -45% (-10%,-20%,-30% milih) | ||||
| Sambungan Generator | Didhukung | ||||
| Output | Sistem Wiring | 3-Fase 5-Kawat | |||
| Dirating Tegangan Output | 380/400/415Vac | ||||
| Faktor Daya Output | 0.9 | ||||
| Akurasi Tegangan | ± 1% | ||||
| Frekuensi | Mode utama: ± 1% / ± 2% / ± 4% / ± 5% / ± 10% luwes; Mode baterei: (50/60±0.1%)Hz | ||||
| Rasio Crest Saiki | 3:1 | ||||
| Tegangan Output THDv | ≤2% (100% beban linier); ≤4% (100% beban non-linear) | ||||
| Efisiensi sakabèhé | 95,5% | ||||
| Overload Capacity | 110% beban: 60min → bypass; 125% beban: 10min → bypass; 150% beban: 1min → bypass | ||||
| Baterei | Tegangan baterei | ±180/192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc (30-50 sel opsional) | |||
| Pengisian Arus | Max 30A | ||||
| Transfer | Wektu Transfer | Daya kanggo lulus: 0ms (tracking); Daya kanggo baterei: 0ms | |||
| Lingkungan | Suhu operasi | 0°C ~ 40°C | |||
| Suhu panyimpenan | -25°C ~ 55°C | ||||
| Range Kelembapan | 0~95% (non-kondensasi) | ||||
| Operating Altitude | <1500m | ||||
| Noise (dB ing 1m) | <60 | ||||
| Fungsi | Fungsi Weker | Kakehan, ora normal listrik, fault UPS, undervoltage baterei, lsp. | |||
| Fungsi Proteksi | Baterei undervoltage, output over/under voltage, short circuit, overload, over temperature, fan fault alarm, surge protection | ||||
| Antarmuka Komunikasi | CAN, RS485, FE, LBS, kertu paralel, adaptor SNMP (opt), kertu relay (opt) | ||||
| fisik | Ukuran (D × W × H mm) | 885×440×1200 | |||
| Bobot Net (kg) | 160 | 162 | 196 | 198 | |
| Standar | Standar sing ditrapake | YD/T 1095-2018 |