+86 13012999975

Usoro 200-600kVA nke ntinye ụzọ atọ na mmepụta UPS nke atọ bụ ọgbọ ọhụrụ nke ntanetị ngbanwe okpukpu abụọ nke ntinye ụzọ atọ na mmepụta UPS atọ. Ọ na-anakwere ihe owuwu modular, njikwa dijitalụ zuru oke yana teknụzụ ọkwa atọ, ma nwee uru dị elu nke arụmọrụ dị elu, njupụta ike dị elu na mma nrụpụta dị mma. Ọ nwere ike iwepụ nsogbu grid dị iche iche ma nye ndị ahịa nchebe ike siri ike na ntụkwasị obi.
IDC (Internet Data Center) ụlọ, nnukwu na ọkara-sized data center, ego center, nnukwu ụlọ ọrụ data center, wdg.
Oke ike: 200-600kVA
Ụdị ọrụ: Ntinye atọ na ntinye atọ
138-485Vac ultra-wide voltaji ntinye na nsonye ntinye obosara nke ukwuu, na-emegharị na gburugburu grid ike siri ike.
Ọrụ mmekọrịta LBS na-enyere aka mmekọrịta nke nkeji abụọ UPS, na-eme ka ntụkwasị obi sistemu dịkwuo elu.
Nakweere topology ọkwa atọ, na-enweta arụmọrụ zuru oke ruru 95.5%6.
Ihe ntinye ike ruru 0.99, ntinye harmonic ugbu a na-erughị 396.
Ikike ibu dị elu, nke nwere ike ijikwa 100% ibu na-adịghị mma, ngbanwe ibu siri ike, yana dakọtara na ndị na-emepụta ọkụ.
Na-akwado nkeji 6 n'otu n'otu yana ịkekọrịta ngwugwu batrị, yana sel batrị 30-50 nwere ike họrọ.
Na-akwado nnwale ịka nká enweghị ibu.
Ihuenyo mmetụ agba 7-inch nwere ihe ngosi eserese, dị mfe iji rụọ ọrụ.
Ọrụ njikwa ọgụgụ isi, na-akwado RS485, SNMP, kọntaktị akọrọ, na oghere CAN.
| Otu | Oke | 33200 (200kVA) | 33300 (300kVA) | 33400 (400kVA) | 33500 (500kVA) | 33600 (600kVA) |
|---|---|---|---|---|---|---|
| Ike | ||||||
| Ike | Enyere ike (kVA) | 200 | 300 | 400 | 500 | 600 |
| Ntinye | ||||||
| Ntinye | Sistemụ waya | 3-Asọ 5- waya | ||||
| Voltaji ntinye akwadoro (Vac) | 380/400/415 | |||||
| Ntinye voltaji (Vac) | 138-485 | |||||
| Oke ntinye ugboro ugboro (Hz) | 40Hz-70 | |||||
| Ihe ntinye ike | > 0.99 | |||||
| Tinye THDi ugbu a | ≤3% (ibu linear 100%) | |||||
| Gafefe oke voltaji | 220Vac elu: 25% (+ 10%, 15%, 20% họrọ); 230Vac elu: 20% (+ 10%, 15% họrọ); 240Vac elu: 15% (+ 10% họrọ); Ala: -45% (-10%, -20%, -30% họrọ) | |||||
| Njikọ Generator | Akwadoro | |||||
| Mpụta | ||||||
| Mpụta | Sistemụ waya | 3-Asọ 5- waya | ||||
| Voltaji arụpụtapụtara akwadoro (Vac) | 380/400/415 | |||||
| Ihe nrụpụta ike | 0.9 | |||||
| Ịdị mma voltaji | ±1% | |||||
| Ugboro (Ụdị isi) | ± 1% / ± 2% / 4% / ± 5% / ± 10% mgbanwe | |||||
| Ugboro (Ụdị batrị) | (50/60 ±0.1%)Hz | |||||
| Ratio Crest dị ugbu a | 3:1 | |||||
| Mpụta Voltage THDv | ≤2% (100% ibu linear); ≤4% (100% ibu na-abụghị linear) | |||||
| N'ozuzu arụmọrụ | 95.5% | |||||
| Ibu Ibu ike | Ibu 110%: 60min → ngafe; Ibu 125%: 10min → ngafe; Ibu 150%: 1 nkeji → ngafe | |||||
| Batrị | ||||||
| Batrị | Voltaji batrị | ± 180/192 / ± 204 / ± 216 / 228 / ± 240 / ± 252 / ± 264 / ± 276 / ± 288 / ± 300Vdc (sel 30-50 nhọrọ) | ||||
| Ọrụ | ||||||
| Ọrụ | Oge mbufe | Isi ihe na-agafe: 0ms (nsochi); Isi na batrị: 0ms | ||||
| Ọrụ mkpu | Ibufe ibu, isi ihe na-adịghị mma, mmejọ UPS, batrị erughị ala, wdg. | |||||
| Ọrụ nchekwa | Batrị undervoltage, mmepụta n'elu/n'okpuru voltaji, mkpirisi sekit, ibufe oke, oke okpomọkụ, mkpu mmejọ fan, nchebe n'elu | |||||
| Nkwukọrịta ozi | CAN, RS485, FE, LBS, parallel card, SNMP adapter (opt), relay card (opt) | |||||
| gburugburu | ||||||
| gburugburu | Okpomọkụ na-arụ ọrụ | 0°C ~ 40°C | ||||
| Okpomọkụ nchekwa | -25°C ~ 55°C | |||||
| Oke iru mmiri | 0 ~ 95% (na-abụghị condensing) | |||||
| Elu arụ ọrụ (m) | <1500 | |||||
| mkpọtụ (dB na 1m) | <65 | <68 | <70 | <70 | <70 | |
| Anụ ahụ | ||||||
| Anụ ahụ | Akụkụ (D×W×H mm) | 850×600×2000 | 850×1200×2000 | |||
| Net arọ (kg) | 335 | 400 | 638 | 740 | 843 | |
| Ọkọlọtọ | ||||||
| Ọkọlọtọ | Ọkọlọtọ dị | YD/T 1095-2018 | ||||